Main MCCB conditions | Alarm contacts |
OFF or ON | ALa 98 (open) ALc 95 (DC+) a ALb 96 (closed) |
Trip | ALa 98 (closed) ALc 95 (DC+) a ALb 96 (open) |
a When DC use, polarity must be considered.
Type of Micro-switch for | Voltage (V AC) | Resistive loads (A) | Inductive load (A) | Voltage (V DC) a | Resistive loads (A) | Inductive load (A) |
AL/AX/ALAX-05–8 | 460 | — | — | 250 | 0.2 | 0.2 |
250 | 3 | 2 | 125 | 0.4 | 0.4 |
125 | 5 | 3 | 30 | 4 | 3 |
AL/AX/ALAX-10 | 460 | 5 | 2 | 250 | 0.3 | 0.3 |
250 | 10 | 10 | 125 | 0.6 | 0.6 |
125 | 10 | 10 | 30 | 10 | 6 |
a When DC use, polarity must be considered.
MCCB type a | Cut-off switch | Voltage (V) b | Input c | Operating time (msec) d |
AC (VA) | DC (W) |
NF32-SV NF63-SV NF63-HV | Equipped | AC 24–48 AC 100–240 AC 380–550 (50/60 Hz) DC 100–125 | 120 | 50 | ≤15 |
NF125-SGV/SEV NF125-HGV/HEV NF125-RGV/UGVNF160-SGV/SEV NF160-HGV/HEV NF250-SGV/SEV NF250-HGV/HEV NF250-RGV/UGV | Equipped | 60 |
NF400-SEW/HEW/REW/UEW NF630-SEW/HEW/REW NF800-CEW/SEW/HEW/REW/UEW | Equipped | AC 24–48/DC 24–48 AC 100–450/DC 100–200 AC 380–550 (50/60 Hz) | 100 V: 20 200 V: 50 330 V: 120 450 V: 170 | 100 V: 10 200 V: 35 | 5–15 |
NF1000-SEW NF1250-SEW NF1600-SEW | Equipped | AC 100–120 AC 200–240 AC 380–450 (50/60Hz) DC 100 | 200 | 70 | 7–15 |
a Also for DSN types.
b Other voltages on request
c For the SHT operating power capacity, any voltage drop in the input electric power must not be below the allowable operating voltage range.
d The operating time includes all the time up to the moment the main contact of the breaker disconnects after a voltage has been applied to the shunt trip devices.
Main MCCB conditions | Auxiliary contacts |
OFF or Trip | AXa 14 (open)AXc 11 (DC+) a AXb 12 (closed) |
ON | AXa 14 (closed)AXc 11 (DC+) a AXb 12 (open) |