Analogni krmilni moduli FX5

Analogni krmilni moduli serije FX5

Analogni vhodni moduli

SpecificationsFX3U-4ADFX5-4ADFX5-8AD
Applicable forBase units FX3G/FX3GC/FX3GE/ FX3U/FX3UC/ FX5U/FX5UCBase units FX5U/FX5UC
Analog channelsInputs448
Outputs
Analog input range-10–10 V DC/-20–20 mA/4–20 mA-10–10 V DC/ -20–20 mA/ 4–20 mA User range setting-10–10 V DC/ -20–20 mA/ Temperature detector (K, J, T, B, R, S, Pt100, Ni100) 2
ResolutionVoltage0.32 mV (16 bit + sign)0.3125 mV0.3125 mV (16 bit + sign)
Current1.25 µA (15 bit + sign)0.625 µA0.625 µA (16 bit + sign)
Fullscale overall accuracy±0.3–1 % 1±0.1–0.3 % 1±0.3–±0.5 %
Power supply5 V DC110 mA (from base unit)40 mA (from base unit)
24 V DC9 mA100 mA (from base unit)100 mA (from external)40 mA (from base unit)
Related I/O points888
Weight kg0.20.20.3
Dimensions (WxHxD) mm55x90x8740x90x8350x90x83
 
Order information Art. no.169508334430312297

1. Dependent on the ambient temperature

Please refer to manuals for further details of specification of temperature detectors.

Notes: The FX2N-8AD can be configured to accept standard analog inputs as well as selected temperature inputs such as K, T or J type thermocouples. To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a ­FX3U-4AD to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

Analogni izhodni moduli

SpecificationsFX3U-4D AFX5U-4D A
Applicable forBase units FX3G/FX3GC/FX3GE/FX3U/FX3UC/FX5U/FX5UCBase units FX5U/FX5UC
Analog channelsInputs
Outputs4
Analog output range-10–10 V DC/0–20 mA/4–20 mA-10–10 V DC/0–20 mA/4–20 mA User range setting
ResolutionVoltage0.32 mV (16 bit + sign)125 µV
Current0.63 µA (15 bit)500 nA
Fullscale overall accuracy±0.3–0.5 %*±0.1–0.3 %*
Power supply5 V DC100 mA (from base unit)
24 V DC160 mA150 mA
Related I/O points8
Weight kg0.2
Dimensions (WxHxD) mm55x90x8740x90x83
 
Order information Art. no.169509325715

* Dependent on the ambient temperature

Notes : To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-4DA to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

Analogni I/O adapterji

SpecificationsFX5-4AD-ADPFX5-4DA-ADP
Analog channelsInputs4
Outputs4
Analog range-10–10 V DC, -20–20 mA-10–10 V DC, 0–20 mA
Resolution312.5 µV/1.125 μA (14 bit )250 µV/1 μA (14 bit )
Overall accuracy±0.1 %*/±0.3 %±0.1 %*/±0.2 %
Power supply5 V DC10 mA (from base unit) 
24 V DC20 mA (from base unit)160 mA (external power supply)
Related I/O points0
Weightkg0.1
Dimensions (WxHxD)mm17.6x90(106)x89.1
 
Order informationArt. no.283559283560

* Dependent on the ambient temperature and signal quality

 

Analogni vhodni temperaturni adapterji

SpecificationsFX5-4AD-PT-ADPFX5-4AD-TC-ADP
Applicable forBase units FX5U, FX5UC
Analog inputs44
Compensated temperature range °C-200–+850 (Pt100)/ -60–+250 (Ni100)-40–+750(J)/ -200–+1200 (K)/ 0–1600(R, S)
Digital outputs-2000–+8500 (Pt100)/ -600–+2500 (Ni100)-400–+7500 (J)/ -2000–+12000 (K)/ 0–16000 (R, S)
Resolution °C0.10.1 (K,J,T), 0.1–0.3 (B,R,S)
Fullscale overall accuracy±0.4–2.4 °C (fullscale)*±2.8–7.2 °C (fullscale)*
Power supply5 V DC10 mA10 mA
24 V DC20 mA20 mA
Related I/O points00
Weight kg0.10.1
Dimensions (WxHxD) mm17.6x90(106)x74(89.1)
 
Order information Art. no.304298304299

* Dependent on the ambient temperature

Notes : When connecting the FX3 analog adapters to a FX3G, FX3S or FX3U base unit, a communications adapter is required. A direct connection without adapter is possible if these modules are connected to a FX3GC, FX3GE or FX3UC base unit.

 

Temperaturni nadzorni moduli

SpecificationsFX5-4LC
Applicable forBase units FX5U, FX5UC
Analog inputs4 (Thermocouple, Pt100 and Pt1000 sensors )
Compensated temperature range°C-200–+2300
Digital outputs4 NPN transistor open collector output points
Resolution°C0.1 °C, 1.0 °C, 0,5 µV or 5.0 µV; Varies depending on input range of used sensors
Fullscale overall accuracy 
Power supply5 V DC140 mA (from base unit)
24 V DC25 mA
Related I/O points8
Dimensions (WxHxD)mm60x90x83
 
Order informationArt. no.312298